Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Post current MO state certificate in machine room 2/26/2021
conversion conversion n/a Repair car top inspection so that it works properly/ down button sticks amd keeps car operating after let go of 2/26/2021
conversion conversion n/a Emergency lighting and alarm not working 2/26/2021
conversion conversion n/a Repair alarm bell 2/26/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Install guard on light top of car 2/26/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 Post current State certificate in machine room 2/26/2021
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Repair stop switch car 6/24/2019
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)3 Install guard on light on top of car 2/26/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 2/26/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 2/26/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service testing & document on log in machine room 2/26/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Repair stop switch in car 2/26/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Need Mcp on site indicating testing procedures located in machine room 10/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency light and alarm bell shall be operational. 5/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Top of car needs to be cleaned. 12/15/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/15/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide monthly fire service testing/log. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts A working car top light shall be provided. 12/15/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Remove all non-elevator related materials from the machine room. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 12/15/2023