Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) All hoisting and governor ropes shall have data tags
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Lighting in overhead where secondary and deflector sheaves are located is not working.
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed. Apply rust prevention treatment to all pit steel, investigate/repair water leak. Remove drain/garden hose that is dripping water into pit. Seal fire penetrations in same wall.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All category 1 testing has been completed EXCEPT UNINTENDED MOTION due to electrical problem with rope gripper, car was left out of service and tesing shall be completed when repairs are completed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Means to resrict car door is not operational. The resrictor is missing from the door.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Complete 5 year test 9/4/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 11/6/2019
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 Change top of car crosshead data tag to show rated speed of 150 rpm 11/6/2019
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Repair emergency light in car 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Repair emergency light in car 6/21/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair light in pit 9/14/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need testing procedures included in MCP on or before 1/1/22 9/14/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 9/14/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service testing and document on log in machine room 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 6/1/2023
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. 6/1/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in the machine room shall be not less than ten foot-candles at floor level. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces A clear path shall be maintained to the overhead/governor. All components requiring maintenance in machinery spaces and control spaces shall have safe and convenient access. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Top of car needs to be cleaned. 12/15/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/15/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide monthly fire service testing/log. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 12/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 12/15/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed. Apply rust prevention treatment to all pit steel, investigate/repair water leak. Remove drain/garden hose that is dripping water into pit. Seal fire penetrations in same wall. 11/14/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 Machine room FAID sump pump alarm needs wiring inside 4x4 box and module installed properly. 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required shall be provided in the machine room. MCP is blank. 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Cartop light does not work. 11/14/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing shall be documented monthly. 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Car door restrictor shall work at all floors (restrictor is missing). 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting shall work. 11/14/2025