MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
The machine room shall be cleaned.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Battery lowering is not working. Take corrective action and re-test.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
conversion
|
conversion
|
n/a
|
|
|
Escape hatch switch needs to be replaced
|
8/15/2018
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
repair emergency light in car/on top of car
|
5/5/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove all non elevator storage rom machine room
|
5/1/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
5/1/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Secure air vent in machine room ceiling
|
5/1/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certiicate in machine room
|
5/1/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove all non elevator storage from machine room
|
6/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Repair top of car emergency exit switch
|
6/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Repair emergency light in car
|
8/9/2021
|
conversion
|
conversion
|
n/a
|
|
|
Repair emergency light in car
|
8/9/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service testing & document on log in machine room
|
10/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
|
|
Need Mcp on site indicating testing procedures located in machine room
|
10/22/2021
|
conversion
|
conversion
|
n/a
|
|
|
Post current Mo state certificate in machine room
|
11/4/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting in machine room shall be at least 10 foot-candles.
|
3/31/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Hole in machine room shall be sealed. Penetration compromises 2 hour fire rating.
|
3/31/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
No keys on site to test stop switch in car while on fire service. In car keyed stop switch shall be tested on fire service for compliance.
|
4/19/2024
|