Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 10/30/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/30/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Battery lowering is not working. Take corrective action and re-test. 10/30/2025
conversion conversion n/a No No Escape hatch switch needs to be replaced 8/15/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Hole in machine room shall be sealed. Penetration compromises 2 hour fire rating. 3/31/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Lighting in machine room shall be at least 10 foot-candles. 3/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Need Mcp on site indicating testing procedures located in machine room 10/22/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No No keys on site to test stop switch in car while on fire service. In car keyed stop switch shall be tested on fire service for compliance. 4/19/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing & document on log in machine room 10/22/2021
conversion conversion n/a No No Post current Mo state certificate in machine room 11/4/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 5/1/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certiicate in machine room 5/1/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Remove all non elevator storage from machine room 6/22/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Remove all non elevator storage rom machine room 5/1/2021
conversion conversion n/a No No Repair emergency light in car 8/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Repair emergency light in car 8/9/2021
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No repair emergency light in car/on top of car 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Repair top of car emergency exit switch 6/22/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Secure air vent in machine room ceiling 5/1/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room door shall be self-closing. 10/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No The machine room shall be cleaned. 10/30/2025