Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Repair/replace hoistway door unlocking device/pull chain box (2nd landing).
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Take corrective action to obtain mac safety rope pull out 5/6/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Repair rope gripper--emergency brake failed 5/14/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate post current state certificate in machine room 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need testing procedures included in MCP on or before 1/1/22 9/14/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair ventilation unit connected to controller in machine room 9/14/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Install signage in car, load class & no passengers 9/14/2021
MO Minimum : Elevators (A) - Hoistways (A)5 Obtain proper pull out safety ropes 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair air conditioner to controller 9/14/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide monthly fire service test & document on log in machine room 9/14/2021
conversion conversion n/a ladder up to machine room need to be bolted down at the bottom 9/14/2021
conversion conversion n/a Need to replace/service fire extinguisher in machine room tagged 1976 9/14/2021
conversion conversion n/a Post Mo State certificate in machine room 9/14/2021
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 Install missing signage in car A loading class B No passengers 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Repair hoistway door lock at 1R to operate as designed. 4/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Governor safety rope pullout shall not exceed 42" (200 fpm or less). Currently pulls 64". Elevator Red Tagged. 5/1/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x 2.17.12.4 - Rope used as a connection from the safety to the governor rope, including rope wound on the safety-rope drum, shall be made of corrosion resistant/non-magnetic metal (bronze, etc). 5/1/2024