Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Put light shall work, a permanent lighting fixture shall be provided in all pits.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency lighting shall work and be of sufficient brightness.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Standby power operation to be tested.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Front gate mechanical bump edge is not working.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The pit light shall work. A permanent lighting fixture shall be provided in all pits. The light is not working.
MO Minimum : Elevators (H) - Machine Rooms (H)8 Electrical box in machine room above light disconnect needs to have cover installed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.7 - Sequence operation 2.13.3.4 2.13.3.4.1 - Freight door audible signal for "auto-close" is not working. Visual signal is working.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Non-elevator related items shall not be stored in machine room. Remove Freon bottles, roofing adhesives, etc.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
conversion conversion n/a Post current Mo state operating certificate in machine room 12/10/2018
conversion conversion n/a Alarm bell not working 12/10/2018
conversion conversion n/a Repair emergency phone 12/10/2018
conversion conversion n/a Repair pit lighting/ lighting shall be permanent fixture 12/10/2018
conversion conversion n/a Repair emergency lighting 12/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone shall work with and without main power and give proper location. Walkie-talkie is not an approved elevator phone. 6/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency lighting shall work and be of sufficient brightness. 6/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Test Incomplete. Standby Power operation to be tested and verified with 100% capacity. 6/4/2024