Post current Mo state operating certificate in machine room
|
12/10/2018
|
conversion
|
conversion
|
n/a
|
|
|
Alarm bell not working
|
12/10/2018
|
conversion
|
conversion
|
n/a
|
|
|
Repair emergency phone
|
12/10/2018
|
conversion
|
conversion
|
n/a
|
|
|
Repair pit lighting/ lighting shall be permanent fixture
|
12/10/2018
|
conversion
|
conversion
|
n/a
|
|
|
Repair emergency lighting
|
12/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Put light shall work, a permanent lighting fixture shall be provided in all pits.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Non-elevator related items shall not be stored in machine room. Remove Freon bottles, roofing adhesives, etc.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit light shall work. A permanent lighting fixture shall be provided in all pits. The light is not working.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Electrical box in machine room above light disconnect needs to have cover installed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.7 - Sequence operation
|
2.13.3.4
|
|
|
2.13.3.4.1 - Freight door audible signal for "auto-close" is not working. Visual signal is working.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Test Incomplete. Standby Power operation to be tested and verified with 100% capacity.
|
6/4/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lighting shall work and be of sufficient brightness.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Standby power operation to be tested.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Front gate mechanical bump edge is not working.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone shall work with and without main power and give proper location. Walkie-talkie is not an approved elevator phone.
|
6/4/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lighting shall work and be of sufficient brightness.
|
6/4/2024
|