Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x A category 5 full load test shall be witnessed in 2020. 9/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 6/23/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 All machine room wiring shall be enclosed. 6/23/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 6/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The movement of the safety drum rope, starting from a fully retracted position, must not exceed 30". (It pulled out 48") 3/1/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Replace burnt out light in the elevator machine room secondary