MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
A category 5 full load test shall be witnessed in 2020.
|
9/8/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
All machine room wiring shall be enclosed.
|
6/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
6/23/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
6/23/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Replace burnt out light in the elevator machine room secondary
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The movement of the safety drum rope, starting from a fully retracted position, must not exceed 30". (It pulled out 48")
|
3/1/2022
|