MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
All machine room wiring shall be enclosed.
|
6/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
6/23/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)9 Capacity Plate
|
|
|
Change car capacity plate to 3500 lbs.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Clean machine room floor of bird droppings.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
6/23/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Mainline junction box shall have a cover installed.
|
12/7/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly Fire Service test and post on log in machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current certificate in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Properly enclose the cab fan wiring.
|
12/7/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide maintenance control program in machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove bird droppings and dead bird from overhead machine room. Machine room floors shall be kept clean and free of grease and oil. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored therein.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Replace knocked out Up Hall Call Button on 9th floor
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
The car door restrictor shall be operational.
|
1/5/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car alarm bell shall be operational on auxiliary power.
|
3/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
3/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
The loose items on the cartop over the door operator and load weighing system shall be removed.
|
6/23/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The unsupported raceway in the overhead shall be properly installed and supported or removed.
|
6/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
|
3/28/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
|
3/24/2025
|