Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 9/29/2020
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x Hoist ropes need to be shortened. Counterweight less than a half inch away from buffer with car level with top floor. 1/6/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP shall be kept in equipment room 9/29/2020
A17.1-1996 : Elevators 2.18 - Traction drive machines 208 x Severe traction loss witnessed during testing. 1/6/2020