Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 10/27/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP shall be kept in equipment room 10/27/2020
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety code concern. Without motion, the switch de-activates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch 8/20/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Firefighters Service is not working properly, elevator goes to basement instead of floor with key switch 1st floor. Re-inspection required 4/26/2024