Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.1 - Door Reopening Device 8.11.3.1.1(a) Door operator has a damaged drive belt which should be replaced 8/3/2020
A17.1-2016 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 8.11.3.1.3(d) Due to clearance btwn cartop and wall of aprox 2ft, a car top handrail should be installed 8/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide code data plate conforming to sec 8.9 11/3/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 11/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide a capacity plate in car 2/2/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service testing a nd document on log in machine room 2/2/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it is also a safety / code concern. Without motion, the switch de-activates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch and replace with a conventional on/off switch.