MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it is also a safety / code concern. Without motion, the switch de-activates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch and replace with a conventional on/off switch.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
11/3/2021
|
A17.1-2016 : Elevators
|
1.1 - Door Reopening Device
|
8.11.3.1.1(a)
|
|
|
Door operator has a damaged drive belt which should be replaced
|
8/3/2020
|
A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
8.11.3.1.3(d)
|
|
|
Due to clearance btwn cartop and wall of aprox 2ft, a car top handrail should be installed
|
8/3/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide code data plate conforming to sec 8.9
|
11/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide a capacity plate in car
|
2/2/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service testing a nd document on log in machine room
|
2/2/2023
|