MO Minimum : Elevators (A) - Hoistways (A)16 There is a broken traveling cable zip tied together.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No maintenance records on site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm does not work. 7/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light does not work. 7/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Car lighting does not work. 7/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Fire extinguisher needs to be in machine room. 2/7/2019
MO Minimum : Elevators (H) - Machine Rooms (H)8 Light switch cover needs to be installed. 2/7/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 Clean machine room of all dirt and debris. 2/7/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing and self locking. 2/7/2019
MO Minimum : Elevators (H) - Machine Rooms (H)3 Gutter water line running over top of controller. 2/7/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lights need to be anchored to ceiling and protective tubes over lights. 2/7/2019
MO Minimum : Elevators (I) - Pits (I)7 There is no stop switch in the pit.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)2 Drum machine needs to be resocketed. Reinspection required.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x SAFETIES BROKEN DURING CAT 5 TEST 12/12/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate NO VALID OPERATING CERTIFICATE POSTED 2/7/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room.