MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
There is a broken traveling cable zip tied together.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm does not work.
|
7/6/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light does not work.
|
7/6/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Car lighting does not work.
|
7/6/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Fire extinguisher needs to be in machine room.
|
2/7/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self closing and self locking.
|
2/7/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)3
|
|
|
Gutter water line running over top of controller.
|
2/7/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Clean machine room of all dirt and debris.
|
2/7/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lights need to be anchored to ceiling and protective tubes over lights.
|
2/7/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Light switch cover needs to be installed.
|
2/7/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
There is no stop switch in the pit.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)2
|
|
|
Drum machine needs to be resocketed. Reinspection required.
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
SAFETIES BROKEN DURING CAT 5 TEST
|
12/12/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
NO VALID OPERATING CERTIFICATE POSTED
|
2/7/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
No maintenance records on site.
|
|