Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Elevator alarm bell not working 11/7/2019
conversion conversion n/a Machine room lights not working 2/14/2020
conversion conversion n/a Elevator pit light is not working 2/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 x Machine room penetrations 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Hoistway penetration NE corner 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 x Install ceiling in machine room 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x Heat and smokes for shunt recall 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits x Increase pit illumination to 10 ft candles throughout measured at the floor. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Enclose top hoistway 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x No oil minder on sump pump. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x Machine room illumination shall be 19 ft candles throughout measured at the floor. 2/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide source power labels on disconnect switches. 5/13/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 5/13/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in equipment room. 5/13/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is expired, have serviced or replaced 7/3/2024