Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 4/1/2024
conversion conversion conversion - red tag Yes Yes Elevator would not remain at floor with 125% capacity. 9/13/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No NEC 620 - Provide a permanent power source to the pit sump pump. 1/1/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.19 - Guide rails fastening and equipment 8.11.2.1.3(y) No No Correct the excessive play between the car guides and the rails. 1/1/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The hatch door unlocking pull chain box shall be lockable at the top and bottom floor. 3/25/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit light shall work. 1/1/2020
MO Minimum : Elevators (I) - Pits (I)8 No No Sump pump hall be covered 11/17/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit lighting shall be made permanent 11/17/2022
MO Minimum : Elevators (I) - Pits (I)8 Yes No Sump pump shall be covered. Re-inspection required 10/7/2022
MO Minimum : Elevators (I) - Pits (I)8 No No Sump pump shall be covered 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access shall be secured 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Machine room shall have permanent and safe access 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lighting in front of controller 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Yes No Machine room lighting in front of controller shall be 10 ft candles. Re-inspection required 10/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)1 Yes No Provide safe and convenient access to the elevator machine room, numerous lights out. Repair/replace as needed. 9/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 Yes No Provide safe and convenient access to the elevator machine room, drain pipe at shin level-relocate. 9/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access shall be secured 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Machine room shall have permanent and safe access 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Properly secure and lock machine room gate. 9/13/2018
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Machine motor piping shall be secured 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room shall have lighting in front of controller 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Need to properly secure & lock machine room gate 4/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Maintenance records shall be kept in the machine room 4/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Elevator electrical prints shall be kept in the machine room 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Maintenance records shall be kept in the machine room 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Yes No Provide code complaint fire extinguisher in the elevator machine room. 9/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Yes No Elevator electrical prints shall be kept in the machine room. Re-inspection required 10/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Provide current year MCP. 4/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Yes No A copy of the MCP shall be kept in the machine room. Re-inspection required 10/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Elevator electrical prints shall be kept in the machine room 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light shall be made operable. Re-inspection required 6/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A copy of the MCP shall be kept in the elevator machine room 11/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be made operable. Re-inspection required 8/4/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 No No Emergency exit shall be bolted down 11/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is inoperable. Re-inspection required 10/7/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required 6/30/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Cab lights shall be guarded. 9/13/2018
MO Minimum : Elevators (A) - Hoistways (A)10 No No Hoistway access boxes shall be made lockable 11/17/2022