Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits NEC 620 - Provide a permanent power source to the pit sump pump. 1/1/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.19 - Guide rails fastening and equipment 8.11.2.1.3(y) Correct the excessive play between the car guides and the rails. 1/1/2020
conversion conversion conversion - red tag x x Elevator would not remain at floor with 125% capacity. 9/13/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Properly secure and lock machine room gate. 9/13/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Cab lights shall be guarded. 9/13/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light shall work. 1/1/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The hatch door unlocking pull chain box shall be lockable at the top and bottom floor. 3/25/2022
MO Minimum : Elevators (I) - Pits (I)8 Sump pump hall be covered 11/17/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit lighting shall be made permanent 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access shall be secured 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)1 Machine room shall have permanent and safe access 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Maintenance records shall be kept in the machine room 11/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 6/30/2022
MO Minimum : Elevators (H) - Machine Rooms (H)7 Machine motor piping shall be secured 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room shall have lighting in front of controller 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Elevator electrical prints shall be kept in the machine room 11/17/2022
MO Minimum : Elevators (A) - Hoistways (A)10 Hoistway access boxes shall be made lockable 11/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Emergency exit shall be bolted down 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light shall be made operable. Re-inspection required 6/30/2022
MO Minimum : Elevators (I) - Pits (I)8 Sump pump shall be covered 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access shall be secured 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)1 Machine room shall have permanent and safe access 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the elevator machine room 11/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall be made operable. Re-inspection required 8/4/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting in front of controller 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Elevator electrical prints shall be kept in the machine room 11/17/2022
MO Minimum : Elevators (I) - Pits (I)8 x Sump pump shall be covered. Re-inspection required 10/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) x A copy of the MCP shall be kept in the machine room. Re-inspection required 10/7/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is inoperable. Re-inspection required 10/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) x Machine room lighting in front of controller shall be 10 ft candles. Re-inspection required 10/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) x Elevator electrical prints shall be kept in the machine room. Re-inspection required 10/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide current year MCP. 4/1/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 4/1/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 x Provide safe and convenient access to the elevator machine room, numerous lights out. Repair/replace as needed. 9/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 x Provide safe and convenient access to the elevator machine room, drain pipe at shin level-relocate. 9/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x Provide code complaint fire extinguisher in the elevator machine room. 9/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Need to properly secure & lock machine room gate 4/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Maintenance records shall be kept in the machine room 4/1/2024