ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
NEC 620 - Provide a permanent power source to the pit sump pump.
|
1/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.19 - Guide rails fastening and equipment
|
8.11.2.1.3(y)
|
|
|
Correct the excessive play between the car guides and the rails.
|
1/1/2020
|
conversion
|
conversion
|
conversion - red tag
|
x
|
x
|
Elevator would not remain at floor with 125% capacity.
|
9/13/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Properly secure and lock machine room gate.
|
9/13/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Cab lights shall be guarded.
|
9/13/2018
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit light shall work.
|
1/1/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The hatch door unlocking pull chain box shall be lockable at the top and bottom floor.
|
3/25/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump pump hall be covered
|
11/17/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit lighting shall be made permanent
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access shall be secured
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Machine room shall have permanent and safe access
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Maintenance records shall be kept in the machine room
|
11/17/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
6/30/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Machine motor piping shall be secured
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room shall have lighting in front of controller
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
Elevator electrical prints shall be kept in the machine room
|
11/17/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
|
|
Hoistway access boxes shall be made lockable
|
11/17/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Emergency exit shall be bolted down
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light shall be made operable. Re-inspection required
|
6/30/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump pump shall be covered
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access shall be secured
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Machine room shall have permanent and safe access
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the elevator machine room
|
11/17/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall be made operable. Re-inspection required
|
8/4/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting in front of controller
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
Elevator electrical prints shall be kept in the machine room
|
11/17/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
x
|
|
Sump pump shall be covered. Re-inspection required
|
10/7/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
x
|
|
A copy of the MCP shall be kept in the machine room. Re-inspection required
|
10/7/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is inoperable. Re-inspection required
|
10/7/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
x
|
|
Machine room lighting in front of controller shall be 10 ft candles. Re-inspection required
|
10/7/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
x
|
|
Elevator electrical prints shall be kept in the machine room. Re-inspection required
|
10/7/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide current year MCP.
|
4/1/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
4/1/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
x
|
|
Provide safe and convenient access to the elevator machine room, numerous lights out. Repair/replace as needed.
|
9/7/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
x
|
|
Provide safe and convenient access to the elevator machine room, drain pipe at shin level-relocate.
|
9/7/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
x
|
|
Provide code complaint fire extinguisher in the elevator machine room.
|
9/7/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Need to properly secure & lock machine room gate
|
4/1/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Maintenance records shall be kept in the machine room
|
4/1/2024
|