ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
8.11.2.1.2(q)
|
|
|
A grease seal on the drive machine is leaking excessively and shall be replaced. Replace grease seal and clean up the drive sheave of lubricant.
|
12/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.7 - Car leveling and anticreep devices
|
8.11.2.1.3(j)
|
|
|
The elevator car top has a noticeable amount of weight added to compensate operational issues. Correct the leveling issues and remove the added extra weight.
|
12/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Take corrective action and re-test.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Car door restrictor does not work, needs repair. Re-inspection required
|
9/8/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency two way communication device is inoperable. Repair or replace
|
4/29/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be clean of all debris
|
5/2/2024
|