Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Take corrective action and re-test.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Water shall not be allowed to accumulate on pit floors.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. 4/20/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit failed to operate during testing. Perform the following tests to complete inspection: full load full speed safeties, unintended motion up direction, full load unintended motion down direction, governor trip speed, governor switch trip speed, governor rope pull out, governor rope pull thru 7/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone in car is not answered. Repair same 7/13/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate needs to be displayed in machine room 7/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired. Replace or have serviced 7/27/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency two way communication device is inoperable. Repair or replace 4/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room has a leaking pipe causing water to leak on floor. Repair leak to maintain a clean machine floor 5/2/2024