Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace seized up counterweight rollers. 10/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide written maintenance control program. 10/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance control program is required. 10/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide a written maintenance control program. 8.6.1.2.1 11/2/2018
MO Minimum : Elevators (I) - Pits (I)2 Counterweight buffer stand is rusted out and not secured. Replace deteriorated buffer stand within 15 days or unit will be removed from service. 10/19/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test car safeties with rated load at rated speed. Re-inspection required 6/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test car safeties with rated load at rated speed. Re-inspection required 10/7/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Full load test has not been completed. Need to test car safeties with rated load at rated speed within 30 days or elevator will be red-tagged and removed from service. Re-inspection required 10/23/2024
conversion conversion n/a Water in pit. 11/2/2018