MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test car safeties with rated load at rated speed. Re-inspection required
|
6/28/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test car safeties with rated load at rated speed. Re-inspection required
|
10/7/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Full load test has not been completed. Need to test car safeties with rated load at rated speed within 30 days or elevator will be red-tagged and removed from service. Re-inspection required
|
10/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Provide a written maintenance control program. 8.6.1.2.1
|
11/2/2018
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Counterweight buffer stand is rusted out and not secured. Replace deteriorated buffer stand within 15 days or unit will be removed from service.
|
10/19/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide written maintenance control program.
|
10/19/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Maintenance control program is required.
|
10/19/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace seized up counterweight rollers.
|
10/19/2020
|
conversion
|
conversion
|
n/a
|
|
|
Water in pit.
|
11/2/2018
|