Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Car alarm bell shall work. 5/22/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Car emergency lighting shall work. 4/6/2020
conversion conversion n/a No No Close in open area aroung hoistway vent. 4/6/2020
conversion conversion n/a No No Door open button not working properpy on Phase II and normal operation. 4/6/2020
conversion conversion conversion - reinspect Yes No Emergecy phone not working. 5/3/2018
conversion conversion n/a No No Need copy of current state operating certificate in machine room. 4/6/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide a code compliant MPC including onsite documents. 7/8/2025
conversion conversion n/a No No Remove oil from pan under pump unit. 4/6/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No There is an abandoned button in the phone box. This button shall be removed. 7/8/2025
conversion conversion conversion - reinspect Yes No Two-way communication shall work. 8/30/2018
conversion conversion n/a No No Updated certificate in machine room. 4/6/2020