MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
Provide NO PASSENGERS signage in car with 1/2" or larger lettering
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing rope guard on governor
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace missing cover on cartop electrical box for car lighting
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)5
|
|
|
Provide car platform guard
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of current state operating certificate needs to be properly displayed in machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)9
|
|
|
Provide a phase reversal device on controller
|
|
conversion
|
conversion
|
n/a
|
|
|
Car top emergency exit shall be constructed of material to withstand 150#, fastened from top of elevator.
|
8/14/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
All hoistway wiring shall be enclosed in metal conduit or flexible conduit.
|
8/14/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)6
|
|
|
The 3rd floor and basement floor electrical interlock needs to be adjusted.
|
8/14/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergencylight in car shall work
|
8/29/2024
|
MO Minimum : Elevators
|
(D) - Brakes
|
(D)2
|
x
|
x
|
Brake failed 125% lower and hold test. Red Tagged
|
8/29/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Perform full load, full speed testing of car safeties
|
8/29/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
x
|
x
|
8.6.4.20.10 Elevator will not lift rated capacity. Red Tagged
|
8/29/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. It is currently lying on the floor, it shall be mounted as required.
|
9/3/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
The data on the door operator tag shall be filled out.
|
9/3/2024
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of Section 8.7.
|
9/3/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
A duplex GFCI receptacle shall be provided in the machine room.
|
9/3/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Feeder locations for the main and lighting branch circuits shall be marked on the disconnects.
|
9/3/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
The machine room shall be provided with permanent lighting providing a minimum illumination of 200 lx (19 fc) at the floor level.
|
9/3/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
All machine room wiring shall be enclosed.
|
9/3/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
The wireway covers shall be installed in the hoistway.
|
9/3/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
The hall buttons, fire service phase one key-switch, and phone monitor have not been permanently installed. Before the elevator can be released for operation, these items must be permanently installed and a re-inspection must be performed.
|
9/3/2024
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
x
|
|
2.11.11.6 - The tabs on the hall door gibs must be turned down into the sill slot.
|
9/3/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. It is currently lying on the floor, it shall be mounted as required.
|
11/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
The data on the door operator tag shall be filled out.
|
11/26/2024
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of Section 8.7.
|
11/26/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
A duplex GFCI receptacle shall be provided in the machine room.
|
11/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Feeder locations for the main and lighting branch circuits shall be marked on the disconnects.
|
11/26/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
The machine room shall be provided with permanent lighting providing a minimum illumination of 200 lx (19 fc) at the floor level.
|
11/26/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
All machine room wiring shall be enclosed.
|
11/26/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
The wireway covers shall be installed in the hoistway.
|
11/26/2024
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
x
|
|
2.11.11.6 - The tabs on the hall door gibs must be turned down into the sill slot.
|
11/26/2024
|