Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x 2.11.11.6 - The tabs on the hall door gibs must be turned down into the sill slot. 9/3/2024
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x 2.11.11.6 - The tabs on the hall door gibs must be turned down into the sill slot. 11/26/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x x 8.6.4.20.10 Elevator will not lift rated capacity. Red Tagged 8/29/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of current state operating certificate needs to be properly displayed in machine room
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of Section 8.7. 9/3/2024
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of Section 8.7. 11/26/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x A duplex GFCI receptacle shall be provided in the machine room. 11/26/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x A duplex GFCI receptacle shall be provided in the machine room. 9/3/2024
MO Minimum : Elevators (A) - Hoistways (A)16 All hoistway wiring shall be enclosed in metal conduit or flexible conduit. 8/14/2019
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x All machine room wiring shall be enclosed. 9/3/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x All machine room wiring shall be enclosed. 11/26/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. It is currently lying on the floor, it shall be mounted as required. 11/26/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. It is currently lying on the floor, it shall be mounted as required. 9/3/2024
MO Minimum : Elevators (D) - Brakes (D)2 x x Brake failed 125% lower and hold test. Red Tagged 8/29/2024
conversion conversion n/a Car top emergency exit shall be constructed of material to withstand 150#, fastened from top of elevator. 8/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergencylight in car shall work 8/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. 9/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. 11/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform full load, full speed testing of car safeties 8/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)9 Provide a phase reversal device on controller
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)5 Provide car platform guard
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 Provide NO PASSENGERS signage in car with 1/2" or larger lettering
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing cover on cartop electrical box for car lighting
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing rope guard on governor
MO Minimum : Elevators (A) - Hoistways (A)6 The 3rd floor and basement floor electrical interlock needs to be adjusted. 8/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x The data on the door operator tag shall be filled out. 9/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x The data on the door operator tag shall be filled out. 11/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The hall buttons, fire service phase one key-switch, and phone monitor have not been permanently installed. Before the elevator can be released for operation, these items must be permanently installed and a re-inspection must be performed. 9/3/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x The machine room shall be provided with permanent lighting providing a minimum illumination of 200 lx (19 fc) at the floor level. 11/26/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x The machine room shall be provided with permanent lighting providing a minimum illumination of 200 lx (19 fc) at the floor level. 9/3/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x The wireway covers shall be installed in the hoistway. 9/3/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x The wireway covers shall be installed in the hoistway. 11/26/2024