Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency lights shall work. 6/7/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall be programmed to a 24 hour source. 5/8/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm bell shall work. 8/27/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be operational. 4/26/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Phase 2 fire service hold feature does not work, car is still able to run. 14 days to repair or will be red tagged per MO AHJ. Elevator not currently red tagged. 4/4/2024