Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on 110v emergency power. Repair or replace 8/10/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Elevator hoisting ropes need to be shortened in order to meet the minimum requirement runby of 6” 8/10/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Car safeties are stopping the car with a 9” slide with a 6” shoe, making the slide only 3”. The minimum stopping distance for the car is 13” after the shoe is subtracted from the actual slide 8/10/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Testing is incomplete and must have the counterweight slide checked and do fire service 8/10/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Car safeties are stopping the car with a 9" slide with a 6" shoe, making the slide only 3". The minimum stopping distance for the car is 13" after the shoe is subtracted from the actual slide. Red- Tagged, Re-inspection required 8/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing is incomplete and mush have the counterweight slide checked and do fire service. Re-inspection required. 8/29/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)4 x x /car safeties are stopping the car with a 9" slide with a 6" shoe, making the slide only 3". The minimum stopping distance for the car is 13" after the show is subtracted from the actual slide. Red tagged, Re-inspection required 9/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing is incomplete and must have the counterweight slide checked and do fire service. Re-inspection required 9/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. 11/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 11/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to. 11/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts A number of guide rollers have degraded to the point of replacement is required on the elevator car and counterweight. Replace the degraded rollers. 11/16/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to. 11/16/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x All units to be tested on emergency power. 11/16/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Main and lighting disconnects need feed location labels. 11/16/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x All FAID to be tested for all units together, reconfigured for current grouping and fire status panel. 11/16/2025