Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 No No Junction box in hoistway shall have a cover
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 No No Fan is required in the cab
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Electrial prints shall be kept on site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 8/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No An ABC fire extinguisher with a current test tag shall be provided in the machine room. 7/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on-site documentation required by A17.1 2016-8.6.1.2.2 & 8.6.1.4 shall be provided in the machine room. 7/10/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room needs more light. Provide code compliant machine room lighting. 7/10/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No MAchine room shall be kept clean and free non-elevator equipment
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Lighting in the machine room shall be not less than 10 foot-candles at the floor level. 7/10/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The machine room shall be kept clean. Clean the machine room. 7/10/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The machine room lighting shall be operational. 8/31/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The machine room shall be kept clean. Only elevator related materials and equipment shall be stored in the machine room. 8/31/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Permanently installed electric lighting shall be provided in all machinery spaces, machine rooms, control spaces, and control rooms. The illumination shall be not less than 200 lx (19fc) at floor level.
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean and dry. Clean the pit. 7/10/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No A pit light and a pit light cover shall be provided in the pit. 7/10/2026
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Clean the pit. 8/31/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational and a cover installed over the light. 8/31/2022
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No Fire hat not lighting up on COP or on hall switch. 7/10/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No The in car stop switch shall be overridden while on Phase 1 fire service. 2/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 6/19/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide a current tested ABC type fire extinguisher in the elevator machine room. 6/17/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate in the elevator machine room. 6/17/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it. 7/10/2026