MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
The pit shall be kept clean. Clean the pit.
|
8/31/2022
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
No
|
No
|
The pit lighting shall be operational and a cover installed over the light.
|
8/31/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
8/31/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/31/2022
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
Lighting in the machine room shall be not less than 10 foot-candles at the floor level.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
The machine room shall be kept clean. Clean the machine room.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
The pit shall be kept clean and dry. Clean the pit.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
No
|
No
|
A pit light and a pit light cover shall be provided in the pit.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
An ABC fire extinguisher with a current test tag shall be provided in the machine room.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
All the on-site documentation required by A17.1 2016-8.6.1.2.2 & 8.6.1.4 shall be provided in the machine room.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
Machine room needs more light. Provide code compliant machine room lighting.
|
7/10/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Display the current state operating certificate in the elevator machine room.
|
6/17/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
No
|
No
|
Provide a current tested ABC type fire extinguisher in the elevator machine room.
|
6/17/2020
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
The machine room lighting shall be operational.
|
8/31/2022
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
The machine room shall be kept clean. Only elevator related materials and equipment shall be stored in the machine room.
|
8/31/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it.
|
7/10/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
MAchine room shall be kept clean and free non-elevator equipment
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
Electrial prints shall be kept on site.
|
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
No
|
No
|
Junction box in hoistway shall have a cover
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
No
|
No
|
Fan is required in the cab
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
Permanently installed electric lighting shall be provided in all machinery spaces, machine rooms, control spaces, and control rooms. The illumination shall be not less than 200 lx (19fc) at floor level.
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
The in car stop switch shall be overridden while on Phase 1 fire service.
|
2/1/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
6/19/2020
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
Yes
|
No
|
Fire hat not lighting up on COP or on hall switch.
|
7/10/2026
|