MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)7
|
x
|
x
|
Provide missing seal on the governor.
|
10/3/2019
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
A category 5 inspection is required.
|
10/3/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 1 & Phase 2 key switches shall be keyed the same.
|
10/3/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The remainder of the annual and category 5 test needs to be completed. The inspection could not be completed due to testing problems on the other elevator being red tagged and removed from service. Note: The hoistway, hoistway door interlocks, gate switch and restrictor, and fire service have been inspected.
|
10/22/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Governor overspeed, governor pull out/pull through, safety test and slide, car buffer, and counterweight buffer must be tested to complete category 5 test.
|
12/5/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Counterweight buffer and governor pullout/pull thru must still be tested to complete category 5 testing.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The lighting in the stairwell that leads to the machine room shall be operational.
|
12/8/2021
|
conversion
|
conversion
|
n/a
|
|
|
Car top needs to be cleaned.
|
1/15/2021
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Door close operation shall require constant pressure on phase 2 fire service.
|
10/1/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase 2 fire service switch in car shall be keyed alike with other fire service switches.
|
10/1/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Return to phase 1 fire service did not work when turning phase 2 switch to off.
|
10/1/2018
|
conversion
|
conversion
|
n/a
|
|
|
Need fire fighters instructions in main lobby.
|
1/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
1/15/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|