Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
conversion conversion conversion - reinspect Yes No Door close operation shall require constant pressure on phase 2 fire service. 10/1/2018
conversion conversion conversion - reinspect Yes No Phase 2 fire service switch in car shall be keyed alike with other fire service switches. 10/1/2018
conversion conversion conversion - reinspect Yes No Return to phase 1 fire service did not work when turning phase 2 switch to off. 10/1/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase 1 & Phase 2 key switches shall be keyed the same. 10/3/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)7 Yes Yes Provide missing seal on the governor. 10/3/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes A category 5 inspection is required. 10/3/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/15/2021
conversion conversion n/a No No Need fire fighters instructions in main lobby. 1/15/2021
conversion conversion n/a No No Car top needs to be cleaned. 1/15/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) No No The lighting in the stairwell that leads to the machine room shall be operational. 12/8/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The remainder of the annual and category 5 test needs to be completed. The inspection could not be completed due to testing problems on the other elevator being red tagged and removed from service. Note: The hoistway, hoistway door interlocks, gate switch and restrictor, and fire service have been inspected. 10/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Governor overspeed, governor pull out/pull through, safety test and slide, car buffer, and counterweight buffer must be tested to complete category 5 test. 12/5/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Counterweight buffer and governor pullout/pull thru must still be tested to complete category 5 testing. 12/6/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 11/21/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/21/2025