Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/15/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The lighting in the stairwell that leads to the machine room shall be operational. 12/8/2021
conversion conversion n/a Need phase 2 fire signage in car. 1/15/2021
conversion conversion conversion - reinspect x Emergency light and bell shall work. 10/1/2018
conversion conversion n/a Position indicator in car shall work 1/15/2021
conversion conversion conversion - reinspect x Return to phase 1 fire service did not work when turning phase 2 switch to off. 10/1/2018
conversion conversion conversion - reinspect x Door close operation shall require constant pressure on phase 2 fire service. 10/1/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x A category 5 inspection is required. 10/3/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 and Phase 2 key switches shall be keyed the same. 10/3/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Provide Phase 2 instructions in the car. 10/3/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency bell shall work. 10/3/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency lights shall work. 1/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Car failed unintended motion test with 125% load, did not stop within allowed distance. Elevator Red Tagged. 10/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Mainline disconnect broke during testing and needs repair. Elevator Red Tagged. 10/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The remainder of the annual and category 5 test needs to be completed. Note: Hoistway, hall door interlocks, car gate switch and restrictor, emergency light, alarm, 2 way-communication, and fire service have been inspected. 10/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x Unit is still under red tag condition. Unintended motion with 125% load and counterweight buffer testing must be performed to complete category 5 testing and remove red tag. 12/5/2024