MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
A category 5 inspection is required.
|
10/3/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
1/15/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Car failed unintended motion test with 125% load, did not stop within allowed distance. Elevator Red Tagged.
|
10/22/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Door close operation shall require constant pressure on phase 2 fire service.
|
10/1/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell shall work.
|
10/3/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency light and bell shall work.
|
10/1/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Emergency lights shall work.
|
1/15/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Mainline disconnect broke during testing and needs repair. Elevator Red Tagged.
|
10/22/2024
|
conversion
|
conversion
|
n/a
|
|
|
Need phase 2 fire signage in car.
|
1/15/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 1 and Phase 2 key switches shall be keyed the same.
|
10/3/2019
|
conversion
|
conversion
|
n/a
|
|
|
Position indicator in car shall work
|
1/15/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Provide Phase 2 instructions in the car.
|
10/3/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Return to phase 1 fire service did not work when turning phase 2 switch to off.
|
10/1/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The lighting in the stairwell that leads to the machine room shall be operational.
|
12/8/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The remainder of the annual and category 5 test needs to be completed. Note: Hoistway, hall door interlocks, car gate switch and restrictor, emergency light, alarm, 2 way-communication, and fire service have been inspected.
|
10/22/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
x
|
Unit is still under red tag condition. Unintended motion with 125% load and counterweight buffer testing must be performed to complete category 5 testing and remove red tag.
|
12/5/2024
|