ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site required documentation (including fire service log) shall be provided in the machine room.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Door close operation shall require constant pressure on phase 2 fire service.
|
10/1/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency alarm bell shall work on battery power
|
10/1/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Return to phase 1 fire service did not work when turning phase 2 switch to off.
|
10/1/2018
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
A category 5 inspection is required.
|
3/5/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 1 and Phase 2 key switches shall be keyed the same.
|
3/5/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell shall work.
|
3/5/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
x
|
|
Provide code compliant machine room lighting.
|
10/3/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
x
|
|
Provide GFCI type receptacle in the machine room.
|
10/3/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Provide a sign on the machine room door.
|
10/3/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
x
|
|
Remove the foreign wires passing through the machine room rear door.
|
10/3/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
x
|
|
Provide code compliant pit lighting.
|
10/3/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
1/15/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Emergency lights shall work.
|
1/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
x
|
Phase 2 fire service shall be operational. - Elevator Red Tagged.
|
8/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
x
|
The lower pit stop switch shall be operational. - Elevator Red Tagged.
|
8/12/2021
|