| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x |  | Emergency alarm bell shall work. | 3/5/2019 | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | x |  | Provide code compliant machine room lighting. | 10/3/2019 | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | x |  | Provide GFCI type receptacle in the machine room. | 10/3/2019 | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x |  | Provide a sign on the machine room door. | 10/3/2019 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | x |  | Remove the foreign wires passing through the machine room rear door. | 10/3/2019 | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | x |  | Provide code compliant pit lighting. | 10/3/2019 | 
                
                    | conversion | conversion | conversion - reinspect | x |  | Door close operation shall require constant pressure on phase 2 fire service. | 10/1/2018 | 
                
                    | conversion | conversion | conversion - reinspect | x |  | Emergency alarm bell shall work on battery power | 10/1/2018 | 
                
                    | conversion | conversion | conversion - reinspect | x |  | Return to phase 1 fire service did not work when turning phase 2 switch to off. | 10/1/2018 | 
                
                    | MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | A category 5 inspection is required. | 3/5/2019 | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | (S)1 | x |  | Phase 1 and Phase 2 key switches shall be keyed the same. | 3/5/2019 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | x | x | Phase 2 fire service shall be operational. - Elevator Red Tagged. | 8/12/2021 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits |  | x | The lower pit stop switch shall be operational. - Elevator Red Tagged. | 8/12/2021 | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) |  |  | A code compliant MCP and all the on-site required documentation (including fire service log) shall be provided in the machine room. |  | 
                
                    | MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting |  |  | Emergency lights shall work. | 1/15/2021 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/15/2021 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.41 - Maintenance Records | 8.6.1.4 |  |  | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) |  |