Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency lights shall work. 1/15/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/15/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits x The lower pit stop switch shall be operational. - Elevator Red Tagged. 8/12/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site required documentation (including fire service log) shall be provided in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x x Phase 2 fire service shall be operational. - Elevator Red Tagged. 8/12/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm bell shall work. 3/5/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) x Provide code compliant machine room lighting. 10/3/2019
MO Minimum : Elevators (H) - Machine Rooms (H)7 x Provide GFCI type receptacle in the machine room. 10/3/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Provide a sign on the machine room door. 10/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x Remove the foreign wires passing through the machine room rear door. 10/3/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Provide code compliant pit lighting. 10/3/2019
conversion conversion conversion - reinspect x Door close operation shall require constant pressure on phase 2 fire service. 10/1/2018
conversion conversion conversion - reinspect x Emergency alarm bell shall work on battery power 10/1/2018
conversion conversion conversion - reinspect x Return to phase 1 fire service did not work when turning phase 2 switch to off. 10/1/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x A category 5 inspection is required. 3/5/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 and Phase 2 key switches shall be keyed the same. 3/5/2019