Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In cab emergency telephone shall work with 24/7 support. 2/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Sheave seals worn and leaking. Repair or replace as needed. 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Interlocks at floors 2 & 5 shall have covers installed. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. 5/5/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x A category 5 inspection is required. 2/18/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x A category 5 full load test is due. Unit will be modernized in March/April. Deputy Chief Gus Guadamuz approved delay in Category 5 test until MOD. 7/27/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 and Phase 2 key switches shall be keyed the same. 2/18/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 x The machines, controller, governor, isolation transformers, and disconnects shall have an identification number or letter painted or engraved, or securely attached, corresponding to the elevator they serve, and shall be a minimum of 2" in height. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) x Equipment in the machine room not being used in conjunction with the function or use of the elevators shall be removed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Machine room wiring shall be enclosed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x All wireway and electrical device covers must be installed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Temporary wiring must be removed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x 2.4.5 - A data plate complying with 2.16.3.3 permanently and securely attached shall be provided in the pit, in the vicinity of the counterweight buffer, indicating the maximum designed counterweight runby. 9/30/2020
conversion conversion conversion - reinspect x Governor rope is severely rusted and shall be replaced. 10/2/2018
conversion conversion conversion - reinspect x Cab emergency telephone does not work and shall be repaired and tested. 10/2/2018
conversion conversion n/a Hoistway door interlock covers are missing on ground, 1st, 2nd, 5th, & 6th floor landings and shall be replaced. 5/5/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate in the elevator machine room. 5/5/2020