Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In cab emergency telephone shall work with 24/7 support. 2/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Sheave seals worn and leaking. Repair or replace as needed. 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Interlocks at floors 2 & 5 shall have covers installed. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean and dry. 5/5/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes A category 5 inspection is required. 2/18/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes A category 5 full load test is due. Unit will be modernized in March/April. Deputy Chief Gus Guadamuz approved delay in Category 5 test until MOD. 7/27/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase 1 and Phase 2 key switches shall be keyed the same. 2/18/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Governors need to be spun and pullout/pull thru test must be performed. 7/11/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 Yes No The machines, controller, governor, isolation transformers, and disconnects shall have an identification number or letter painted or engraved, or securely attached, corresponding to the elevator they serve, and shall be a minimum of 2" in height. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) Yes No Equipment in the machine room not being used in conjunction with the function or use of the elevators shall be removed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No Machine room wiring shall be enclosed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No All wireway and electrical device covers must be installed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No Temporary wiring must be removed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No 2.4.5 - A data plate complying with 2.16.3.3 permanently and securely attached shall be provided in the pit, in the vicinity of the counterweight buffer, indicating the maximum designed counterweight runby. 9/30/2020
conversion conversion conversion - reinspect Yes No Governor rope is severely rusted and shall be replaced. 10/2/2018
conversion conversion conversion - reinspect Yes No Cab emergency telephone does not work and shall be repaired and tested. 10/2/2018
conversion conversion n/a No No Hoistway door interlock covers are missing on ground, 1st, 2nd, 5th, & 6th floor landings and shall be replaced. 5/5/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 5/5/2020