Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x A category 5 full load test is due. Unit will be modernized in March/April. Deputy Chief Gus Guadamuz approved delay in Category 5 test until MOD. 9/30/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x A category 5 inspection is required. 2/18/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
conversion conversion conversion - reinspect x Car shall return to phase 1 fire service operation when turning phase 2 switch to off. 10/2/2018
conversion conversion conversion - reinspect x Door close shall require constant pressure on phase 2 fire service. 10/2/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm bell shall work. 2/18/2020
conversion conversion conversion - reinspect x Emergency light and alarm shall work. 10/2/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency lights shall work. 5/5/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 and Phase 2 key switches shall be keyed the same. 2/18/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 fire service instructions are required in the car. 2/18/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate in the elevator machine room. 5/5/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 The car top exit shall be properly secured. 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation The car top light shall be operational. 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency bell shall operate with 110v source removed. 9/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The hoistway door closers shall operate properly. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational. 5/5/2020