Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Door close operation shall require constant pressure on phase 2 fire service. 10/2/2018
conversion conversion conversion - reinspect Yes No Car shall return to phase 1 when turning phase 2 switch to off. 10/2/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Hoistway door closers shall operate properly. 2/18/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes A category 5 inspection is required. 2/18/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase 1 and Phase 2 key switches shall be keyed the same. 2/18/2020
MO Minimum : Elevators (F) - Electrical Switches (F)3 Yes No Car operating panel is damaged and shall be repaired or replaced as needed. 2/18/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes A category 5 full load test is due. Unit will be modernized in March/April. Deputy Chief Gus Guadamuz approved delay in Category 5 test until MOD. 2/18/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase 1 fire service shall be operational. - Unit Red Tagged 2/18/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The fan located in the elevator cab shall be guarded. 5/5/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 5/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The fan located in the elevator cab shall be guarded. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational. 5/5/2020
conversion conversion n/a No No In car position indicator shall work. 5/5/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational. 5/5/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes A category 5 full load test is due. Unit will be modernized in March/April. Deputy Chief Gus Guadamuz approved delay in Category 5 test until MOD. 7/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Hoistway door closers shall operate properly. 7/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No Machine room wiring shall be enclosed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No All wireway and electrical device covers must be installed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No Temporary wiring must be removed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No The receptacles in the machine room shall be of the GFCI type. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) Yes No Equipment in the machine room not being used in conjunction with the function or use of the elevators shall be removed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No 2.4.5 - A data plate complying with 2.16.3.3 permanently and securely attached shall be provided in the pit, in the vicinity of the counterweight buffer, indicating the maximum designed counterweight runby. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 Yes No The machines, controller, governor, isolation transformers, and disconnects shall have an identification number or letter painted or engraved, or securely attached, corresponding to the elevator they serve, and shall be a minimum of 2" in height. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 Yes No The governor rope shall have tags installed. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 Yes No The suspension ropes shall have tags installed. 9/30/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Governors need to be spun and pullout/pull thru test must be performed. 7/11/2025