Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Counterweight buffer test needs to be performed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light does not work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Lobby Hall call buttons do not work.
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Bottom car door does not hit open limit during Phase I fire service recall. Car will not do anything unless doors are manually opened. Red tagged elevator.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No There needs to be fire service instructions inside the car and at the recall key switch.
conversion conversion conversion - reinspect Yes No Emergency phone in topar not working 5/7/2019
conversion conversion n/a No No Phase one Fire service not working 9/23/2019