Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Brakes will not hold 125% capacity. Must be repaired and retested. Red-tag issued. 7/31/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not function properly, parts missing. (Multi-year violation)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting shall work.
conversion conversion conversion - reinspect x Fire Service to be tested at later date. 3/22/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Perform fire service operation testing. Phase I and II 3/28/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide testing of the elevator on emergency power and selector switch. (Multi-year violation)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing door gib on 14th floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing door gibs on 14th floor. 7/31/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete due to red-tag. Items to still be tested: all weight tests, slide, pullout rope length, fire service, door pressure, emergency power (if applicable). If not completed within 60 days, all of this inspections results will be voided and repeated. 7/31/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: replace CO2 extinguishers in machine room and secondary machine room with ABC type extinguishers. (Multi-year violation)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation Compliant/required documentation & MCP shall be kept in equipment room (neat/organized) including wiring diagrams, and fire service log, recorded monthly. Note: No PM log, callback log, repair log, testing records, or fire service test logs for 2022 - 2025.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoist rope tail retaining clips shall be properly spaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoist rope tail retaining clips shall be properly spaced. (Multi-year violation)
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting needs to be repaired. One or more bulbs are not working.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace missing door gibs on floor 14. 2/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Secondary machine room fire extinguisher shall have current monthly/annual test tag.