Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Brakes will not hold 125% capacity. Must be repaired and retested. Red-tag issued.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete due to red-tag. Items to still be tested: all weight tests, slide, pullout rope length, fire service, door pressure, emergency power (if applicable). If not completed within 60 days, all of this inspections results will be voided and repeated.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace missing door gibs on floor 14. 2/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing door gibs on 14th floor.
MO Minimum : Elevators (S) - Fire Service (S)1 x Perform fire service operation testing. Phase I and II 3/28/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Secondary machine room fire extinguisher shall have current monthly/annual test tag.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoist rope tail retaining clips shall be properly spaced.
conversion conversion conversion - reinspect x Fire Service to be tested at later date. 3/22/2019