Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes Yes Governor safety rope pull out exceeds 30" maximum allowable (68" actual pull out). Elevator Red Tagged. 12/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete; Items still needed: all weight tests, buffer tests, governor speeds, governor pullout/pull-thru, slide, fire service, door pressure, EP. Must be completed within 60 days. 12/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 9/29/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete; Items still needed: all weight tests, buffer tests, governor speeds, governor pullout/pull-thru, slide, fire service, door pressure, EP. 9/29/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 3/3/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Provide testing or elevator on emergency power selector switch. Was not tested in 2025.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes Yes 2-way communication is not working. Elevator red tagged as this violation first cited in 2022 and is still not corrected. 12/3/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2 way communication is not working. Re-inspection required 11/18/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 No No Car top emergency exit shall be properly secured.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 No No Emergency exit shall be properly secured. 3/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light and alarm bell do not work. 6/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light inoperative, repair. 3/28/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Repair inoperative emergency light. 2/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Repair inoperative emergency phone. 2/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency lighting is not working. Re-inspection required 11/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes Yes Emergency lighting is not working. Elevator red tagged as this violation first cited in 2022 and is still not corrected. 12/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency lighting is not working. 9/29/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lighting needs to be repaired. One or more bulbs are not working. 3/3/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lighting needs to be repaired. One or more bulbs are not working. 9/29/2025
MO Minimum : Elevators (H) - Machine Rooms (H)6 No No Overspeed governors in secondary shall be numbered to their corresponding machines.
MO Minimum : Elevators (H) - Machine Rooms (H)6 No No Machinery, controllers, governors, disconnects shall be numbered. All governors need to be numbered. 3/3/2026
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Remove excess debris. 3/3/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be kept clean.
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Perform fire service operation testing. Phase I and II 3/28/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State operating certificate shall be displayed in the machine room in a non-combustible frame.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No PM/callback/repair logs, or testing records for 2022-2025. 3/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 9/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Compliant/required documentation shall be provided in the machine room. PM log, callback log, repair log, testing records, and monthly fire service testing log.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Replaced CO2 fire extinguisher in machine room and secondary spaces with ABC type. Multi-year violation. 3/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current ABC type fire extinguisher shall be provided in the secondary machine room. 9/29/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Fire service shall be tested and documented monthly. No log for 2022-2025. 3/3/2026
conversion conversion conversion - reinspect Yes No Fire service to be tested at a later date. 3/22/2019