Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No PM/callback/repair logs and no testing records 2022-2025.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Brake failed to hold 125% static load at floor level (drifted to buffer). RED TAG ISSUED.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work. 6/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor shall work at all floors. Restrictor plunger removed and laying on cartop.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and bell do not work. 6/2/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service shall be tested and documented monthly. No log for 2022-2025.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting needs to be repaired. One or more bulbs are not working.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light shall work.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Items to still be tested: All weight tests (100% & 125%), slide, pullout rope length, fire service, door pressure, and finals (CW Buffer passed). If not completed within 90 days, all of the completed inspection results will be voided and must be repeated.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Tighten/repair car interior handrail.