Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. The phone dials, but no answer.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictors shall work at all floors. Some parts are missing or disabled.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not function properly. 6/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoist rope tail retaining clips shall be properly spaced.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Brakes will not hold 125% capacity. Must be repaired or retested. Red-tag issued.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Items to still be tested: all weight tests, slide, pullout rope length, fire service, door pressure, finals, and emergency power (if applicable). If not completed within 60 days, all of this inspections results will be voided and repeated.
conversion conversion conversion - reinspect x Did not test fire service 3/28/2019