MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
A pit ladder shall be installed in the pit. The ladder shall extend not less than 30" above the sill of the access floor. The ladder shall be made of non-combustible material. The ladder that is installed for this pit is unsafe and is not code compliant. 30 Days to correct violation and have a re-inspection, per MO AHJ.
|
6/7/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Car and cwt, butters w/ full load, safties w/ full load, 125% break, emergency lighting, alarm bell, emergency phone, and door pressure must be tested to complete CAT 5 testing.
|
2/25/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Code compliant machine room lighting shall be provided.
|
1/14/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
1/14/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State operatinf certificate is on-site but need to be in a non-combustible frame and placed in the machine room. It is now posted in the mechanical area outside of the machine room.
|
2/25/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a code compliant MCP including onsite documents.
|
2/8/2021
|