MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a code compliant MCP including onsite documents.
|
2/8/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Code compliant machine room lighting shall be provided.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
A pit ladder shall be installed in the pit. The ladder shall extend not less than 30" above the sill of the access floor. The ladder shall be made of non-combustible material. The ladder that is installed for this pit is unsafe and is not code compliant. 30 Days to correct violation and have a re-inspection, per MO AHJ.
|
6/7/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|