Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/14/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x A pit ladder shall be installed in the pit. The ladder shall extend not less than 30" above the sill of the access floor. The ladder shall be made of non-combustible material. The ladder that is installed for this pit is unsafe and is not code compliant. 30 Days to correct violation and have a re-inspection, per MO AHJ. 6/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Code compliant machine room lighting shall be provided. 1/14/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State operating certificate is on-site but needs to be in a non-combustible frame and place in the machine roo. It is now posted in the mechanical area outside of the mahcine room. 1/21/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Gov spin test, safies w/ full load, emergency light, alarm bell, emergency phone, and door pressure must be tested to complete CAT 5 testing. 1/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. 2/8/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Unit has been RED TAGGED due to governor tripping to soon. Eletrical swtich and jaws tripping at lower speed than indicated on governor data tag. Governor must be adjusted to trip at speed consistent with data tag and then sealed. 1/21/2026