Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. (From MO AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas". 6/9/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log MCP Fire service testing must be properly documented monthly on log sheet.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace missing "Do not use elevator in case of fire" signage on first floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/9/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track (third floor).