MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
An ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/24/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
8/24/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency telephone shall be operational.
|
9/12/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is expired.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
In the stairway leading up to the roof where the machine room is located there is a step that has a significant crack from end to end. Once on the roof there are also other steps that are damaged. These steps shall be repaired to provide safe and convenient access to the machine room.
|
8/24/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair machine room lighting.
|
6/10/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
There is an excessive amount of water in the pit that shall be removed. The pit shall be kept clean and dry.
|
8/24/2023
|
MO Minimum : Elevators
|
(J) - Counterweights
|
(J)2
|
|
|
Counterweight slide guides are wore out and not usable. counterweights getting ready to come off guide rails. Elevator removed from service. Reinspect before use.
|
6/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
|
|
A permanent and unobstructed means of access to elevator machine rooms and overhead machinery spaces shall be provided. The top of the stairway leading to the roof isn't lighted, and should be.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
The machine room temperature shall be kept within the manufacturers recommended range. The air conditioner is not working.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
The key switches required by 2.27.3 for all elevators in a building shall be operable by the same key. The two elevators in the building are using different fire service keys. They should be keyed the same.
|
9/24/2024
|
conversion
|
conversion
|
n/a
|
|
|
Repair machine room lighting
|
6/10/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
There is no state operating certificate displayed in the machine room.
|
10/10/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
8/24/2023
|